2817 0764 / 0763 / 0762 / 0761
bps.meet@gmail.com
An ISO 9001 : 2008 Certified

BPS 10KVA to 20KVA True On Line UPS(3 – 1)

Product Description

10KVA to 20KVA True On Line UPS

Key Features:

  • True double-conversion
  • Microprocessor control optimizes reliability
  • Output power factor 0.8 / 0.9
  • Wide input voltage range
  • Cold start function
  • Emergency power off function (EPO)
  • Generator compatible,
  • User friendly digital LCD display
  • SNMP+USB+RS-232 multiple communications
  • 3-stage extendable charging design for optimized
    battery performance
  • Advanced battery management

 

Technical Specification Of 10KVA to 20KVA True On Line UPS:

MODEL BPSLF10 BPSLF15 BPSLF20
CAPACITY 10KVA/8000W 15KVA/12000W 20KVA/16000W
INVERTER TYPE IGBT Based DSP Technology
INPUT Voltage Range 400V/415V/440V AC ±20%, (3Ph+N+PE)
Frequency 46Hz-54Hz
Power Factor ≥0.98
OUTPUT Voltage 230V AC,Single Phase
Voltage Regulation ±1%
Load Regulation ±2%
Frequency 50Hz ± 0.2Hz
Power Factor 0.8 Standard / 0.9 Optional
Waveform Pure Sine Wave
Total Harmonic Distortion < 3%  Linear load, < 5%  non linear load
Crest Factor 3∶1
Overload Capability 10 Minutes at 110% load, 5 Minutes at 120%
Efficiency(on line mode) >90%
BATTERY DC Voltage 192 VDC /216 VDC / 240 VDC /360 VDC
Recharge Current Adjustable Adjustable Adjustable
Transfer Time 0ms (AC mode→Battery mode)
Noise Level (1m) <45dB
Ambient Temperature 0~45℃
Duty Cycle Continuous
Cooling Forced air cooling
Bypass Switch Static bypass switch / Manual bypass Switch (Optional)
Humidity 0~95% (Non-condensing)
Sea Level Elevation <1500m
Metering LCD Display input/output Voltage, Frequency, Battery voltag, Battery capacity, Loading rate.
Protections  Input, Output – Low and High , Battery low and high voltage, Input, output – MCB, Transient Surge,Battery – MCB/Fuse, Short circuit, Over load,Temperature
Trip Conditions Over load, Over and Under voltage, Short Circuit,low battery,Over Temperature
Indications Mains ON, Inverter ON, Battery Low, Overload.
Isolation
Transformer
Internally / Externally ( Optional)
Alarms Audio for extreme battery low voltage / Mains fail
Communication Smart RS232, SNMP(Optional),USB (Optional)
Emergency Switch OFF Emergency Switch OFF Avilable ( Optional)
*Specification and ups image are subject to change without notice due to constant improvement in design & technology.